E30E084 | 84-ckt solid-core pwr/energy IP meter | 100A CTs | 3/4"spacing | Veris
100 A 100 to 277 VAC Line-to-Neutral, 300 VAC Circuit Multi-Circuit Advanced with Ethernet Panelboard Monitoring System, Solid-Core, 84-Circuit with 3/4 in Spacing
Documents and manuals
Overview
Details for E30E084
84-ckt solid-core pwr/energy IP meter | 100A CTs | 3/4"spacing
FEATURES
- Revenue grade measurements
- ANSI & IEC Class 1 metering system accuracy including branch CTs
- Solid-core branch CT strip models for new construction
- Split-core branch CT models for retrofit applications
- Reports volts, amps, power, demand, & energy for each circuit...one product covers up to two complete 42 breaker panelboards*
- Up to 92 circuits with one product (84 branch circuits, 2 3-phase mains, 2 neutrals*)...saves space
- User configurable meters provide multi-phase totals for loads with any combination of 1, 2, 3 pole breaker positions
- 3/4”, 1”, or 18 mm spaced solid-core branch CT strips... flexible installation
- 4 user-configurable alarm threshold registers...improved load management
- Selectable orientation and numbering of the circuits
- 50mA to 100A monitoring...widest dynamic range in the industry
- Modbus RTU standard on all models
- Modbus TCP over ethernet is standard on E3xExxx models and available on others with addition of U013-0012
- BACnet IP (with BBMD support) or MS/TP is standard on E3xExxx models and available on others with addition of E8951
- SNMP support is standard on E3xExxx models and available on others with addition of E8951
SPECIFICATIONS
INPUTS
Input Power 100-277VAC, 50/60 Hz, 15VA max.
ACCURACY
Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008. 1% system accuracy (includes main board and branch CTs)
Voltage ±0.5% of reading 90-277VAC line-to-neutral
Current ±0.5% of reading
Minimum ON Current 50mA
OPERATION
Sampling Frequency 2560 Hz
OUTPUTS
Serial Protocols
All: Modbus RTU
E3xE models: BACnet MSTP
Serial Connection
All: 2-wire, RS-485
E3xA/B/C models: 4-wire RS-485
Address
E3xA/B/C models: Selectable address 1 to 247 (uses 2 addresses for Modbus RTU)
E3xE models: Selectable at address 1 to 247 for Modbus RTU; 0-127 for BACnet MS/TP
Baud Rate
All: 9600, 19200, 38400 (selectable on A/B/C models)
Parity
All: Modbus RTU: NONE, ODD, EVEN (selectable on A/B/C models)
E3xE models: BACnet MS/TP: NONE (fixed)
Terminal Block Torque 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
Ethernet Protocols
All: Modbus TCP
E3xE models: BACnet IP, SNMP V2c
Ethernet Connection
E3xE models only: RJ-45 10/100 Mbit
ENVIRONMENTAL
Operating Range 0° to 60°C (32° to 140°F) (<95% RH non-condensing)*
Storage Temp Range -40° to 70°C (-40° to 158°F)
Altitude of Operation 3000 m
Agency Approvals UL508, EN61010-1, Cat. III, pollution degree 2
DESCRIPTION
The E3x Series Panelboard Monitoring System provides a cost effective solution for electrical load management, making it ideally suited for applications where loads are dynamic, such as the data storage industry, lighting panels, etc.
The E3x series monitors the current, voltage, instantaneous power, demand, and energy consumption of each circuit in a panelboard including the main feed.** As a circuit approaches the user-configured thresholds, alarm indicators are triggered, preventing costly downtime from overloaded circuits or failed loads. (See graph, facing page)
* E3xE models monitor only current values.
APPLICATIONS
- Load-based cost allocation
- Overload protection
- Data center PDUs
- Subtenant billing
- Lighting control panels
- Load management
- Load balancing
- Energy management
Specifications
Item Number | E30E084 |
Brand | Veris |
Accuracy | 1% System; +/-0.5% of Reading 90 to 277 VAC Line-to-Neutral Voltage; +/-0.5% of Reading from Current |
Communication | ModBus (RTU) | BACnet (MS/TP) |
Dimensions | 10.0" (253 mm) W x 13.9" (353 mm) L x 2.8" (71 mm) H |
Environmental Conditions | Humidity Range: Less Than 95% RH Non-Condensing; Storage Temperature: -40 to 158 °F; Altitude of Operation: 3000 m |
Feature Level | Enhanced (kWh + IP) |
Frequency Rating | 50 - 60 Hz |
Metering Product Family | E30 Panel Meter |
Monitored Voltage Range | 100 - 277 VAC; Line to Neutral |
Mounting | Solid-Core |
Operating Temperature | 32 - 140 °F |
Output Specifications | Modbus RTU/BACnet MSTP;2 or 4 wire; RS485 |
Power Monitoring | Branch Current Monitor - Solid Core |
Product Type | Panelboard Monitoring System; Multi-Circuit; Advanced with Ethernet |
Range | E30 |