H8163-0300-2-2 | Energy Meter | Two CT | 300Amp | Output:Pulse | Phase Loss | Veris (OBSOLETE)
300 A 90 to 300 VAC Line-to-Neutral Input 100 mA at 24 VAC/DC Pulse Output Small Energy Meter, 2-Circuit
Documents and manuals
Veris H8163-0300-2-2 Documents
Overview
Details for H8163-0300-2-2
Energy Meter | Two CT | 300Amp | Output:Pulse | Phase Loss
Description
The H81xx Series Energy Meters are easy to install & provide exceptional system accuracy, making them ideal for all submetering applications.
Each meter is factory-matched with one to three split-core CTs. The meter/CT pairs are system-calibrated to provide excellent total system accuracies of 1% from 2% to 100% of the amperage rating of the CTs (e.g., 2-100 amps with 100 amp CTs).Matching serial numbers assure that the meter and CT were calibrated together (matching does not apply if using 100A CTs).
The H81xx is easy to install. The split-core CTs virtually eliminate the need to remove electrical conductors, reducing installation time. The meter is also capable of detecting and correcting phase reversal, eliminating the need for concern about CT load orientation. The convenient color coding of the CTs and voltage leads make correct connection simpl
Specifications
Item Number | H8163-0300-2-2 |
Brand | Veris |
Accuracy | 1% System; +/-1.0% of Reading from 2% to 100% of rated current of the CT's |
Communication | ModBus (RTU) | Pulse kYZ |
Dimensions | 7.6" (193 mm) W x 8.3" (211 mm) L x 3.0" (77 mm) H |
Display Type | LCD |
Environmental Conditions | Humidity Range: Less Than 95% RH Non-Condensing; Storage Temperature: -40 to 158 °F; Altitude of Operation: 3000 m |
Frequency Rating | 50 - 60 Hz |
Metering Product Family | Energy Meter |
Monitored Voltage Range | 120 - 480 VAC |
Mounting | Panel Mount |
Operating Temperature | 32 - 122 °F |
Output Specifications | Pulse: 100 mA at 24 VAC/DC |
Power Monitoring | H8163 Enhanced Energy Meter |
Product Type | Energy Meter; Small CT; 2-Circuit |
Range | H81XX |