Scroll to view all
Get your Special Pricing!
BCPMC084S | BCPM Power Monitoring Basic - 84 Solid Core 100 A - 19 mm CT Spacing | Square D
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to BCPMC084S
Overview Details for BCPMC084S
BCPM Power Monitoring Basic - 84 Solid Core 100 A - 19 mm CT Spacing
This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for use in new build and is used for critical power operations in data centres and energy management in buildings. It offers class 1 (1 %) power and energy system accuracy (100A solid core current transformers) on all branch channels. The BCPM monitors only the 84 branch circuits current. All to provide information on the complete Power Distribution Unit. Full alarming capabilities ensure that potential issues are dealt with before they become problems. Communication enabled with a RS485 serial port and the Modbus protocol support, more communication options with the gateway H8951. The meter need to be powered by a 90V AC to 277V AC supply source. Include 4 21-CTs board strips with 3/4inch (19mm) spacing between each CT connectors, for 84 circuits. The device dimensions are 228mm in width, 146mm in height and weight 1.5 kilograms.Specifications
- range
- PowerLogic
- product name
- PowerLogic BCPM
- Product or Component Type
- Multi-circuit energy meter
- device short name
- BCPMC
- Model type
- Basic
- power monitoring
- Basic instrumentation
- energy management
- Sub billing and cost allocation
- Device Application
- Sub billing
- type of measurement
- Current
- [Us] rated supply voltage
- 90...277 V AC 50/60 Hz +/- 1 %
- Network Frequency
- 60 Hz;50 Hz
- current transformer input
- 84 solid core CT 100 A
- update time
- 1.8 s
- measurement voltage
- 90…277 V phase to neutral;150…480 V phase to phase
- measurement accuracy
- Current 2 % 0.25…2 A;Current 1 % 2…100 A
- sampling rate
- 256 samples/cycle
- connection pitch
- 0.75 in (19 mm)
- provided equipment
- 84 x current transformer;4 x cables
- communication port protocol
- Modbus RTU
- communication port support
- RS485
- communication of data
- High-high current alarm;Low-low current alarm;High current alarm;Low current alarm
- Mounting Mode
- Panel-mounted
- Mounting Support
- Panel;Enclosure
- relative humidity
- 0…95 % 32…140 °F (0…60 °C)
- Ambient Air Temperature for Storage
- -40…158 °F (-40…70 °C)
- Operating altitude
- 9842.52 ft (3000 m)
- Standards
- UL 508;IEC 61036;EN 61010;ANSI C12.1
- product certifications
- UL
- Width
- 11.34 in (288 mm)
- Height
- 5.75 in (146 mm)
- Net Weight
- 3.31 lb(US) (1.5 kg)
- Category
- 09793-PLOGIC BRANCH CIRCUIT BCPM & MCM
- Discount Schedule
- PL1
- GTIN
- 3606480299582
- Returnability
- No
- Country of origin
- US
- Unit Type of Package 1
- PCE
- Number of Units in Package 1
- 1
- Package 1 Height
- 6.26 in (15.9 cm)
- Package 1 Width
- 9.76 in (24.8 cm)
- Package 1 Length
- 31.26 in (79.4 cm)
- Package 1 Weight
- 9.97 lb(US) (4.523 kg)
- Warranty
- 18 months