Documents: RHP-3O2B
RHP-3O2B | OSA mount 3% RH/temperature transmitter with 0-10 VDC RH output and 10K type II NTC thermistor temperature output. | Dwyer
OSA mount 3% RH/temperature transmitter with 0-10 VDC RH output and 10K type II NTC thermistor temperature output.
Overview Details for RHP-3O2B
OSA mount 3% RH/temperature transmitter with 0-10 VDC RH output and 10K type II NTC thermistor temperature output.
SERIES RHP HUMIDITY/TEMPERATURE TRANSMITTER
The Series RHP Temperature and Humidity Transmitter combine the voltage or current humidity transmitter output with a passive temperature thermistor or RTD output. Featuring polymer capacitance humidity sensors, models are available in 2%, 3% or 5% accuracies. Duct mounted transmitters are available with an optional two-line alpha numeric LCD display.
For models with resistive thermistors or RTD outputs, please click here for temperature to resistance lookup tables.
NIST CALIBRATION available in Product Configurator.
Product Applications
- Air economizers
- Outdoor temperature and relative humidity reference
- Pool room humidity monitoring
- 2%, 3%, or 5% accuracy models
- Optional LCD display on duct mount models
- Radiation shield option for outdoor installation in direct sunlight
Specifications
- Series
- RHP HUMIDITY/TEMPERATURE TRANSMITTER
- Category/Type
- Air Quality
- Type
- Humidity / Temperature Transmitters
- Series
- RHP HUMIDITY/TEMPERATURE TRANSMITTER
- Relative Humidity Range
- 0 to 100% RH.
- Temperature Range
- -40 to 140°F (-40 to 60°C).
- Accuracy; RH
- RHP-2XXX ±2% 10 to 90% RH @ 25°C;RHP-3XXX ±3% 20 to 80% RH @ 25°C;RHP-5XXX ±5% 20 to 80% RH @ 25°C.
- Accuracy; Thermistor Temp Sensor
- ±0.2°C @ 25°C (±0.36°F @ 77°F).
- Accuracy; RTD Temp Sensor
- DIN Class B; ±0.3°C @ 0°C (±0.54°F @ 32°F).
- Accuracy; Solid State Band Gap
- ±0.9°F @ 77°F (±0.5°C @ 25°C).
- Hysteresis
- ±1%.
- Repeatability
- ±0.1% typical.
- Temperature Limits
- -40 to 140°F (-40 to 60°C).
- Storage Temperature
- -40 to 176°F (-40 to 80°C).
- Compensated Temperature Range
- -4 to 140°F (-20 to 60°C).
- Power Requirements
- 4-20 mA loop powered models: 10-35 VDC; 0-5/10 V outputmodels: 15-35 VDC or 15-29 VAC.
- Output Signal (Model Dependent)
- 4-20 mA; 0-5/10V @ 5 mA max.
- Response Time
- 15 s.
- Electrical Connections
- Removable screw terminal block.
- Conduit Connection
- Duct Mount: 1/2" NPS; OSA: 1/2" (22.3 mm).
- Drift
- <1% RH/year.
- RH Sensor
- Capacitance polymer.
- Temperature Sensor
- >Types 1; 2; 3: Solid state band gap;Curves A;B;C; Thermistor; Curves D;E; Platinum RTD DIN 385. (See R-T Lookup Table).
- Enclosure Material
- Duct mount sensor tube: PVC-UL 94 V-0; Duct mount sensorcap: Polycarbonate ABS blend-greater than UL 94 V-0; Duct mount electronicshousing and cover: Makrolon® polycarbonate-UL 94V-HB; OSA: Polycarbonate.
- Enclosure Rating
- Duct mount: NEMA 4X (IP66) for housing only; OSA: NEMA 4X (IP66).
- Display
- Duct Mount only; optional 2-line alpha numeric; 8 characters/line.
- Display Resolution
- RH: 0.1%; 0.1°F (0.1°C).
- Weight
- Duct Mount: .616 lb (.3 kg) OSA: 1 lb (.45 kg).
- Agency Approvals
- CE.