CLS2-W11RK1-019 | Capacitive level switch | weatherproof | 19
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!

Web Price:

$745.77
Availability: This product is currently available to purchase

Contact us for price breaks on large quantities!

Orders over $999 ship FREE*
*Free shipping applies within the continental US and weighing less than 50 lbs. Shipping and Returns Terms
Ship to Estimates
Are you from Chicago?
Yes / No
This item ships to
Change
Cancel


*shipping cost are estimated until you complete your order

The product is not cancelable or returnable unless found defective

Speak With a Technical Expert

Image for Technical Expert

CLS2-W11RK1-019 | Capacitive level switch | weatherproof | 19" probe | Dwyer

Capacitive level switch, weatherproof, 19" probe

Brand: DwyerSKU: CLS2-W11RK1-019
Dwyer | CLS2-W11RK1-019
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to CLS2-W11RK1-019

Overview Details for CLS2-W11RK1-019

See catalog product page for full listing

Capacitive level switch | weatherproof | 19" probe

Series CLS2 Capacitive Level Switch

Powder, Bulk, or Liquids, Auto-Calibration

The Series CLS2 Capacitive Level Switch is a capacitive technology level switch which can be used for liquids, powders and bulk materials. It is offered with PVDF and 316 SS wetted material, weatherproof enclosure, DPDT output and a variety of process connections.

Product Applications

    • Sewage and wastewater
    • Food and beverage
    • Pharmaceuticals
    • Sumps
    • Boilers and steam generators
    • Caustics and acids
    • Reservoirs
 
 

 

  • Automatic Calibration: No need to turn calibration pots, just push the calibration button. The CLS2 even has an external magnet to activate the calibration without having to open the enclosure.
  • Universal Power Supply: One model works from 12 to 240 VAC/DC without any jumpers or settings.
  • Coat Guard: Unit is not affected by sticky, dusty, or clingy materials that coat or build up on the probe preventing false alarms.
  • Failsafe Setting: Output switches can be set for Normally Open or Normally Closed condition on loss of power.
  • Status Indication: Ultra high brightness external red LED switch status indicator, and internal indicators for power, sensor, and switch status that can be seen externally with window cap option (external LED on weatherproof model only).
  • Time Delay: Prevent false alarms from material splashing, agitation, etc.
  • Removable Terminals: Removable terminal block snaps in and out enabling easy wiring outside of the enclosure.
  • No Moving Parts: Permitting for no jams, no wear, nothing to break, and no maintenance.
  • Impulse RF: Admittance measurement combined with an active guard, provides excellent level measurement and stability while being insensitive to material buildup.
  • Immune To: External RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic systems.
  • Can Be Used For: Liquid interface applications to detect the level of two immiscible liquids that have different dielectric constants such as oil and water.
  • Wetted Materials: PVDF and 316 SS assure great chemical compatibility and meet food grade requirements.

Specifications

Series
CLS2 Capacitive Level Switch
Category/Type
Level
Type
Level Switches
Series
CLS2 Capacitive Level Switch
Service
Liquids; powder and bulk materials compatible with wetted materials.
Wetted Materials
316 SS and polyvinylidene fluoride (PVDF).
Temperature Limits
Ambient: -40 to 185°F (-40 to 85°C); -4 to 185°F (-20 to85°C) with under 24 VAC/DC power supply; Process: -40 to 250°F (-40 to 121°C).
Pressure Limit
365 psi (25 bar).
Enclosure Rating
Weatherproof; NEMA 4X.
Switch Type
DPDT (two form C).
Electrical Rating
8 A @ 120/240 VAC res.; 30 VDC. 1/2 hp @ 120 VAC and 1/4 hp @ 240 VAC ind.
Power Requirements
12 to 240 VAC/DC.
Power Consumption
2.8 Watts max.
Electric Connections
1/2" NPT conduit opening; screw termination and removable terminal block.
Process Connection
See Catalog Page.
Mounting Orientation
Vertical or horizontal.
Set Point Adjustment
Trips when product touches probe. Cut or extend probe to length of desired trip point. Can be cut as short a 1" and can be extended by welding on to probe. (Minimum length will be effected by material being sensed.)
Response Time
0.2 s.
Time Delay
Adjustable; 0 to 60 s.
Spark/Static Protection
10 MEG Ohm dissipation resistance with spark gap. Surge current to 100A max.
Sensitivity
8 selectable settings; 1; 2; 4; 6; 8; 10; 14; 20 pF (at 30 pF nominal free capacitance).
Agency Approvals
cULus.