Boiler Control - One tN4, Four Modulating Boiler & DHW / Setpoint
The Boiler Control 275 is designed to stage up to four condensing or non-condensing, modulating or on-off boilers using P.I.D. staging to accurately maintain temperature. Water temperature is controlled by Outdoor Temperature Reset for space heating applications or a fixed setpoint for Domestic Hot Water (DHW) tank heating or industrial process heating applications. The control will also accept an analog 0-10 V (dc) signal from an Energy Management System (EMS) to control the water temperature. Boiler Equal Run Time Rotation, pump exercising and stand-by system pump operation increase boiler plant reliability. The control is tekmarNet® communication compatible allowing for internet connectivity using an optional Gateway 483. Replacement option: 294 Smart Boiler Control, Four tN4, Four Boiler, DHW, Setpoint, Web/Mobile App Notification.
Features
- Outdoor temperature reset, programmable schedules
- Boiler pump(s) operation (optional), test sequence to ensure proper component operation
- Equal run time rotation, exercising
- Powered system pump output, alerts
- Access levels
- tekmarNet® 4 compatible, condensing and non-condensing boiler groups
- DHW pump operation, DHW priority (optional)
- Control up to 4 modulating or on/off boilers, primary pump sequencing
- warm weather shut down, automatic boiler differential
Specifications
Item Number | 275 |
Brand | Tekmar |
Category | Boiler / DHW Controls |