PG-153-P2 | Gas pressure/differential pressure switch | range 0.5-5 psid (.03-.345 bar) | max. deadband 0.4 psid (0.38 bar) | SPDT mercury switch. | Dwyer
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!
Availability: Get a Quote
The product is not cancelable or returnable unless found defective

Speak With a Technical Expert

Image for Technical Expert

PG-153-P2 | Gas pressure/differential pressure switch | range 0.5-5 psid (.03-.345 bar) | max. deadband 0.4 psid (0.38 bar) | SPDT mercury switch. | Dwyer

Gas pressure/differential pressure switch, range 0.5-5 psid (.03-.345 bar), max. deadband 0.4 psid (0.38 bar), SPDT mercury switch.

Brand: DwyerSKU: PG-153-P2
Dwyer | PG-153-P2
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to PG-153-P2

Overview Details for PG-153-P2

See catalog product page for full listing

Gas pressure/differential pressure switch | range 0.5-5 psid (.03-.345 bar) | max. deadband 0.4 psid (0.38 bar) | SPDT mercury switch.

Series PG Gas Pressure/Differential Pressure Switch

External Adjustment, Visible Dial, Hermetically Sealed Snap or Mercury Switch

Large sensitive diaphragm and reliable, time proven mechanical design are combined in Series PG Gas Pressure/Differential Pressure Switches. For use with air and other compatible gases, they feature excellent ±1% of full scale repeatability, clear easy-to-read scale and convenient external setpoint adjustment.

Application flexibility is assured by a large variety of switching options including SPST, SPDT, DPST and DPDT; opening or closing on increasing pressure, vacuum or differential. PR and PRL models add manual reset operation on increasing or decreasing pressure. Mercury switches or hermetically sealed snap switches are available where high humidity would be a problem. If vibration or other factors preclude the use of mercury, snap switches can be provided. Standard housing is NEMA 1. Optional enclosures can be supplied for weather resistant requirements.

California Residents:  Click Here for Proposition 65 WARNING.

Product Applications

  • Natural, manufactured or LP gas applications
  • Clear easy-to-read scale and external set point adjustment simplifies operation and trouble shooting
  • Large diaphragm provides accuracy for precise control
  • Multiple switching options meet the design of applications

Specifications

Series
PG Gas Pressure/Differential Pressure Switch
Category/Type
Pressure
Type
Differential Pressure
Series
PG Gas Pressure/Differential Pressure Switch
Wetted Materials
Fairprene; brass; steel; and aluminum.
Temperature Limits
-10 to 180°F (-23 to 82°C).
Pressure Limit
Single Pressure Use on High Side: sustained pressure: 15 psig (1.0 bar); surge limit: 20 psig (1.4 bar). Differential Pressure Use: sustained pressure; range P1: 2 psig (.14 bar); sustained pressure; range P2: 10 psig (0.7 bar).
Enclosure Rating
General purpose. Weatherproof optional.
Repeatability
±1% of full range.
Switch Type
See Ordering page.
Electrical Rating
See Ordering page.
Electrical Connections
Screw type.
Conduit Connection
7/8" (22.23 mm) hole for 1/2" (12.7 mm) conduit hub.
Process Connection
1/2" male NPT and 1/8" female NPT used for single positive pressure or high differential pressure; 1/8" female NPT used for single vacuum or low differential pressure.
Mounting Orientation
Vertical.
Set Point Adjustment
External screw.
Weight
4.5 lb (2 kg).
Deadband
See Ordering page.
Agency Approvals
UL; FM for mercury switch models. UL only on snap switch models.