Scroll to view all
Get your Special Pricing!
Documents: LC1K1210F7
LC1K1210F7 | TeSys K Contactor, 3-Poles (3 NO), 1 NO Aux. Contact, 12A, 110V AC Coil, Non-Reversing | Square D by Schneider Electric
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to LC1K1210F7
Overview Details for LC1K1210F7
TeSys K Contactor, 3-Poles (3 NO), 1 NO Aux. Contact, 12A, 110V AC Coil, Non-Reversing
TeSys K ContactorSpecifications
- range
- TeSys
- Product or Component Type
- Contactor
- product name
- TeSys K
- device short name
- LC1K
- Device Application
- Control
- contactor application
- Resistive load;Motor control
- utilisation category
- AC-3;AC-4;AC-1;AC-3e
- poles description
- 3P
- power pole contact composition
- 3 NO
- [Ue] rated operational voltage
- Power circuit 690 V AC 50/60 Hz;Signalling circuit <= 690 V AC 50/60 Hz
- [Ie] rated operational current
- 20 A 122 °F (50 °C)) <= 440 V AC AC-1 power circuit;12 A<= 440 V AC AC-3 power circuit;16 A 158 °F (70 °C)) 690 V AC AC-1 power circuit;12 A<= 440 V AC AC-3e power circuit
- control circuit type
- AC 50/60 Hz
- [Uc] control circuit voltage
- 110 V AC 50/60 Hz
- motor power kW
- 4 kW 480 V AC 50/60 Hz AC-3;4 kW 500...600 V AC 50/60 Hz AC-3;4 kW 660...690 V AC 50/60 Hz AC-3;2.2 kW 400 V AC 50/60 Hz AC-4;3 kW 220...230 V AC 50/60 Hz AC-3;5.5 kW 380...415 V AC 50/60 Hz AC-3;5.5 kW 440 V AC 50/60 Hz AC-3;4 kW 480 V AC 50/60 Hz AC-3e;4 kW 500...600 V AC 50/60 Hz AC-3e;4 kW 660...690 V AC 50/60 Hz AC-3e;3 kW 220...230 V AC 50/60 Hz AC-3e;5.5 kW 380...415 V AC 50/60 Hz AC-3e;5.5 kW 440 V AC 50/60 Hz AC-3e
- auxiliary contact composition
- 1 NO
- [Uimp] rated impulse withstand voltage
- 8 kV
- overvoltage category
- III
- [Ith] conventional free air thermal current
- 20 A 122 °F (50 °C) power circuit;10 A 122 °F (50 °C) signalling circuit
- Irms rated making capacity
- 110 A AC signalling circuit IEC 60947;144 A AC power circuit NF C 63-110;144 A AC power circuit IEC 60947
- rated breaking capacity
- 110 A 440 V IEC 60947;80 A 500 V IEC 60947;70 A 660...690 V IEC 60947
- [Icw] rated short-time withstand current
- 115 A 122 °F (50 °C) - 1 s power circuit;105 A 122 °F (50 °C) - 5 s power circuit;100 A 122 °F (50 °C) - 10 s power circuit;75 A 122 °F (50 °C) - 30 s power circuit;55 A 122 °F (50 °C) - 1 min power circuit;50 A 122 °F (50 °C) - 3 min power circuit;80 A - 1 s signalling circuit;90 A - 500 ms signalling circuit;110 A - 100 ms signalling circuit;25 A 122 °F (50 °C) - >= 15 min power circuit
- associated fuse rating
- 25 A gG <= 440 V power circuit;25 A aM power circuit;10 A gG signalling circuit IEC 60947;10 A gG signalling circuit VDE 0660
- average impedance
- 3 mOhm - Ith 20 A 50 Hz power circuit
- [Ui] rated insulation voltage
- Power circuit 600 V UL 508;Power circuit 690 V IEC 60947-4-1;Signalling circuit 690 V IEC 60947-4-1;Signalling circuit 690 V IEC 60947-5-1;Signalling circuit 600 V UL 508;Power circuit 600 V CSA C22.2 No 14;Signalling circuit 600 V CSA C22.2 No 14
- insulation resistance
- > 10 MOhm signalling circuit
- inrush power in VA
- 30 VA 68 °F (20 °C))
- hold-in power consumption in VA
- 4.5 VA 68 °F (20 °C))
- heat dissipation
- 1.3 W
- control circuit voltage limits
- Operational 0.8...1.15 Uc 122 °F (50 °C));Drop-out 0.2...0.75 Uc 122 °F (50 °C))
- connections - terminals
- screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid;screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end;screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end;screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid;screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end;screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end
- maximum operating rate
- 3600 cyc/h
- auxiliary contacts type
- Instantaneous 1 NO
- signalling circuit frequency
- <= 400 Hz
- minimum switching current
- 5 mA signalling circuit
- minimum switching voltage
- 17 V signalling circuit
- Mounting Support
- Rail;Plate
- tightening torque
- 7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2;7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm;7.08…11.51 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2
- operating time
- 10...20 ms coil de-energisation and NO opening;10...20 ms coil energisation and NO closing
- safety reliability level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1;B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- non overlap distance
- 0.02 in (0.5 mm)
- mechanical durability
- 10 Mcycles
- electrical durability
- 0.3 Mcycles 20 A AC-1 <= 440 V;1.3 Mcycles 12 A AC-3 <= 440 V;1.3 Mcycles 12 A AC-3e <= 440 V
- mechanical robustness
- Shocks contactor closed;on X axis10 Gn for 11 ms IEC 60068-2-27;Shocks contactor closed;on Y axis15 Gn for 11 ms IEC 60068-2-27;Shocks contactor closed;on Z axis15 Gn for 11 ms IEC 60068-2-27;Shocks contactor opened;on X axis6 Gn for 11 ms IEC 60068-2-27;Shocks contactor opened;on Y axis10 Gn for 11 ms IEC 60068-2-27;Shocks contactor opened;on Z axis10 Gn for 11 ms IEC 60068-2-27;Vibrations contactor closed4 Gn;5...300 Hz IEC 60068-2-6;Vibrations contactor opened2 Gn;5...300 Hz IEC 60068-2-6
- Height
- 2.28 in (58 mm)
- Width
- 1.77 in (45 mm)
- Depth
- 2.24 in (57 mm)
- Net Weight
- 0.40 lb(US) (0.18 kg)
- standards
- BS 5424;IEC 60947;NF C 63-110;VDE 0660
- Product Certifications
- CSA;UL;UKCA
- IP degree of protection
- IP2x VDE 0106
- protective treatment
- TC IEC 60068;TC DIN 50016
- Ambient Air Temperature for Storage
- -58…176 °F (-50…80 °C)
- operating altitude
- 6561.68 ft (2000 m) without derating
- flame retardance
- V1 conforming to UL 94;Requirement 2 conforming to NF F 16-101;Requirement 2 conforming to NF F 16-102
- Category
- 22326-CTR;K-LINE;AC;OPEN;NONREV
- Discount Schedule
- I12
- GTIN
- 3389110789751
- Returnability
- Yes
- Country of origin
- ID
- Unit Type of Package 1
- PCE
- Number of Units in Package 1
- 1
- Package 1 Height
- 2.56 in (6.5 cm)
- Package 1 Width
- 1.89 in (4.8 cm)
- Package 1 Length
- 2.44 in (6.2 cm)
- Package 1 Weight
- 6.35 oz (180.0 g)
- Unit Type of Package 2
- S02
- Number of Units in Package 2
- 50
- Package 2 Height
- 5.91 in (15 cm)
- Package 2 Width
- 11.81 in (30 cm)
- Package 2 Length
- 15.75 in (40 cm)
- Package 2 Weight
- 20.53 lb(US) (9.313 kg)
- Package 3 Height
- 30.31 in (77 cm)
- Warranty
- 18 months