Documents: RPME-C-005
RPME-C-005 | Room pressure monitor | 1% accuracy | range 0-2.5" wc | Dwyer (OBSOLETE)
Room pressure monitor, 1% accuracy, range 0-2.5" wc
Overview Details for RPME-C-005
Room pressure monitor | 1% accuracy | range 0-2.5" wc
Series RPME Room Pressure Monitor
The Series RPME Room Pressure Monitor is designed for lowdifferential pressure applications that require stringent pressure monitoring andalarming. The Series RPME room pressure monitor can be configuredto monitor positive or negative pressure in protected environments and cleanmanufacturing areas. The RPME room pressure monitor is a completesystem with a fixed segment LCD which enables access to pressure, security,calibration, and alarm setup. The RPME has a brushed stainless steel bezel thatallows for easy cleaning.
The RPME room pressure monitor has built-in status indication LEDsthat will appear green when within the user-defined pressure set range and will appearorange when outside of the pressure set range. 2 SPDT independent control relayswith adjustable deadbands are also provided along with a 4-20 mA process output.
Product Applications
- Clean manufacturing areas
- Clean rooms
- Research labs
- Vivariums
- 2 SPDT relays allow for capability of local alarming and alarming to control system
- Automatic or manual alarm reset
- Visual LED alarms provide immediate local alert allowing corrective action to betaken quicker to eliminate the problem from becoming widespread
- Stores peak and valley process readings
- Same installation diameter as Magnehelic® gage which simplifies field upgrade toRPME room pressure monitor
- Password protected setup menu ensures no errors by untrained personnel
Specifications
- Series
- RPME Room Pressure Monitor
- Category/Type
- Pressure
- Type
- Room Status Monitors
- Series
- RPME Room Pressure Monitor
- Service
- Air and non-combustible; compatible gases.
- Measurement Technology
- Piezoresistive.
- Wetted Materials
- Consult factory.
- Housing Material
- Die cast aluminum case and SS bezel.
- Accuracy
- ±0.5% RSS (includes non-linearity: ±0.49%; hysteresis: ±0.05% andnon-repeatability: ±0.05%); or ±1% RSS (includes non-linearity: ±0.99%; hysteresis:±0.05% and non-repeatability: ±0.05%).
- Pressure Limits
- Ranges 0.5 and 1.0 in w.c: 9 psi; Ranges 2.5 and 5 in w.c.: 1.5psi.
- Temperature Limits
- 32 to 140°F (0 to 60°C).
- Compensated Temperature Limits
- 32 to 140°F (0 to 60°C).
- Thermal Effects
- 0.020%/°F (0.036/°C) from 77°F (25°C).
- Power Requirements
- 12-28 VDC; 12-28 VAC 50 to 400 Hz.
- Power Consumption
- 3 VA max.
- Output Signal
- 4-20 mA DC into 900 Ω max.
- Zero and Span Adjustments
- Accessible via menus.
- Response Time
- 8 ms.
- Display
- Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status.
- Electrical Connections
- 15-pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included.
- Process Connections
- 1/8" female NPT. Side or back connections.
- Mounting Orientation
- Mount unit in vertical plane. Size: 4-3/4" (120.7 mm) OD x 2-21/32 (67.5 mm).
- Weight
- 1.75 lb (794 g).
- SWITCH SPECIFICATIONS
- Switch Type
- 2 SPDT relays.
- Electrical Rating
- 1 A @ 30 VAC/VDC.
- Set Point Adjustment
- Adjustable via keypad on face.