685-07-V | Differential pressure transmitter | 0-25" wc | 0-10 V output | Dwyer
Differential pressure transmitter, 0-25" wc, 0-10 V output
Overview Details for 685-07-V
Differential pressure transmitter | 0-25" wc | 0-10 V output
Series 685 Differential Pressure Transmitter
The Series 685 Differential Pressure Transmitter is used to measure differentialpressure and vacuum. The adjustable pressure range and output signal make it theideal choice for installers and maintenance professionals. It has a user-configurableresponse time via a jumper and can be mounted in any orientation. Applicationsinclude building automation systems, clean room monitoring, valve and flap control,filter monitoring, and air flow control. It has an adjustable pressure range, a singlebutton to zero, and can be reset to factory settings with a long button press. Noadditional reference pressure sources or separate calibration devices are necessary.
Product Applications
- Building automation, air-conditioning and clean room technology
- Valve and shutter control
- Filter, ventilator and fan monitoring
- Air-flow control
- Cost effective and compact device suitable for OEM applications where space, simplicity, and value are key
- Single button to zero saves maintenance time
- Factory restore to defaults with a long button press
- User-adjustable response time provides versatility for many applications
Specifications
- Series
- 685 Differential Pressure Transmitter
- Category/Type
- Pressure
- Type
- Differential Pressure
- Series
- 685 Differential Pressure Transmitter
- Service
- Air and non-corrosive gases.
- Sensor Type
- Piezoresistive pressure sensor.
- Output Signal
- 2-wire: 4-20 mA; 3-wire: 0-10 V.
- Supply Voltage
- 2-wire: 18-30 VDC; 3-wire: 18-30 VAC/DC
- Loop Resistance
- 2-wire: 500 Ω max; 3-wire: ≥ 1 kΩ (≤ 10 mA)
- Maximum Current Draw
- 2-wire: 21 mA; 3-wire: 40 mA.
- Accuracy*
- ≤ ±0.5% RSS (BFSL); ± 1Pa.
- Thermal Effects*
- See model-dependent specifications table.
- Long-Term Stability*
- ≤ ±1% RSS per year.
- Temperature Limits
- -4 to 158°F (-20 to 70°C).
- Humidity Limits
- 0 to 95% RH; non-condensing.
- Response Time
- 1 s (default) or 200 ms (user selectable).
- Pressure Connections
- 6 mm hose connection.
- Electrical Connection
- Spring connector for cable and leads up to 1.5 mm² .
- Cable Conduit
- Cap nut conduit; 15 mm (across flats); made of polyamide.
- Mounting
- Screw fastening with sheet metal screws.
- Housing Material
- ABS.
- Housing Dimensions
- Ø 66 x 28 mm.
- Enclosure Rating
- IP54.
- Weight
- 1.6 oz (46 g).
- Compliance
- CE; UKCA.