Documents: SDR-480-48
SDR-480-48 | 480 Watt Series / 48 VDC / 10.0 Amps Industrial Slim High-Efficiency Single Output DIN Rail Power Supply | Antaira
480 Watt Series / 48 VDC / 10.0 Amps Industrial Slim High-Efficiency Single Output DIN Rail Power Supply
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to SDR-480-48
Overview Details for SDR-480-48
480 Watt Series / 48 VDC / 10.0 Amps Industrial Slim High-Efficiency Single Output DIN Rail Power Supply
480W Single Output Industrial DIN RAIL with PFC FunctionFeatures
- High efficiency 94% and low power dissipation
- 150% peak load capability
- Built-in active PFC function, PF>0.94
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508(industrial control equipment)approved
- EN61000-6-2(EN50082-2) industrial immunity level
- Built-in DC OK relay contact
- 100% full load burn-in test
- 150% peak load capability
- 3 years warranty
Included
- SDR-480-48
Specifications
- AC Input Voltage
- 90~264VAC; 127~370VDC
- AC Inrush Current
- 40A/115VAC, 80A/230VAC
- DC Adjustment Range
- *Please See Datasheet
- DC Output Voltage
- 48V
- Dimensions
- 85.5 x 125.2 x 128.5 mm
- Efficiency
- *Please See Datasheet
- EMC (EN61000-3-2)
- EN61000-3-2, 3
- EMC (EN61000-4-2)
- EN61000-4-2, 3, 4, 5, 6, 8, 11
- EMC (EN61000-6-2)
- EN61000-6-2
- EMS (EN55022)
- Compliance to EN55022 (CISPR22) Class B
- EMS (EN61204-3)
- EN61204-3, heavy industry level, criteria A, SEMI F47 criteria A, GL approved
- EMS (ENV50024)
- ENV55024
- EMS (ENV50204)
- ENV50204
- Hold Up Time
- 14ms/230VAC at full load
- Operating Temperature
- -25 ~ 70 °C (refer to output derating curve)
- Over Voltage Protection
- *Please See Datasheet
- Overload Protection
- 110% ~ 150% rated output power
- R&N
- *Please See Datasheet
- Rise
- 3000ms, 150ms/115VAC at full load
- Safety Standards
- UL508, TUV EN60950-1 approved
- Setup
- 1500ms, 150ms/230VAC
- Tolerance
- *Please See Datasheet
- Warranty
- 3 Years
- Weight
- 1.6 Kg
- Withstand Voltage
- I/P-O/P:3KVAC, I/P-FG:1.5KVAC, O/P-FG:0.5KVAC, O/P-DC OK:0.5KVAC