Scroll to view all
Get your Special Pricing!
PW2XN03S | Pressure | Wet | 2 | Nema 4 | NIST | 0-50PSID | Veris
12 to 24 VDC Input 4 to 20 mA Output Wet Media Differential Pressure Transducer, 0 to 50 psig, NIST
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to PW2XN03S
Overview Details for PW2XN03S
The PW2 series 2-wire, 4 to 20 mA wet pressure transducers incorporate microprocessor profiled sensors for exceptional accuracy and reliability. Easy to use and designed to provide exceptional installation savings, the PW2 series is ideal for measuring pressure across pumps, filters, heat exchangers, compressors and other non-corrosive wet media applications.
- The jumper-selectable output switch for normal (4 to 20 mA) or reverse (20 to 4 mA) operation provides application flexibility
- Rugged, die-cast enclosure provides NEMA 4 sealing
- Selectable differential units: psid or bard
- Dual sensor design for improved overpressure tolerance, eliminates the requirement for a bypass valve assembly in most applications
- Jumper-controlled electronic surge dampening for high stability
- Pushbutton zero calibration - no trim pots to adjust, maintain accuracy and reduce callbacks with automatic zero calibration
- 2-wire transmitter output
- User-selectable output
- NIST certified
- 2 times of maximum full scale range proof pressure
- 5 times of maximum full scale range burst pressure
Optional Accessories: AA14A, AA11, AA12, AA13
Specifications
Item Number | PW2XN03S |
Brand | Veris |
Application Zone | Plant Room |
Application | Pump and Compressor Differential Pressure | Chiller Differential Pressure Monitoring |
Brand | Veris |
Burst Pressure | 250 psi (17 bar) |
Calibration Certificate | NIST Certificate |
Dimension Depth | 2.2" (56 mm) |
Dimension Height | 4" (102 mm) |
Dimension Width | 5.8" (147 mm) |
Direction | Unidirectional |
Display Type | None |
Electrical Wiring | 2-wires (loop-powered) |
Enclosure Material | Powder Coated Aluminium |
Fitting Material | Stainless Steel |
Fitting Size | 1/ 8” NPT |
Fitting Type | Female |
IP Protection | IP65 (NEMA 4) |
Measurement Type | Differential Pressure |
Medium | Water |
Model | PW2XN03S |
Mounting | Panel |
Operating Current | 29 mA |
Operating Humidity | 0 - 90% RH; non-condensing |
Operating Temperature | 14 - 130 °F (-10 - 55 °C) |
Output Specifications | 4 - 20 mA |
Outputs | Analog output |
Pressure Measurement Accuracy | Range A; B and C: ±1% of F.S. Range D: ±2% of F.S. |
Pressure Measurement Range | 0 - 5 psi (0 - 0.3 bar) | 0 - 10 psi (0 - 0.7 bar) | 0 - 25 psi (0 - 1.7 bar) | 0 - 50 psi (0 - 3.5 bar) |
Pressure Range | 0-50 psid |
Pressure Sensor Type | Differential (wet to wet) |
Product Certification | CE |
Product Type | Sensor |
Range | PW2 |
Sensor | Pressure |
Standards EMC | EN 61000-6-1 |
Supply Voltage DC Range | 12 - 24 VDC |
Warranty | 5 years |