Scroll to view all
Get your Special Pricing!
Documents: HW2LA2K
HW2LA2K | RH,Wall,LCD,2%,Temp,10k w/11kS | Veris
Sensor, RH, Wall, LCD,2%,Temp, 10K Thermistor w/11K Shunt
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to HW2LA2K
Overview Details for HW2LA2K
RH,Wall,LCD,2%,Temp,10k w/11kS
Specifications
Item Number | HW2LA2K |
Brand | Veris |
Color | Matte White |
Display Size | 2.05 in (52 mm) |
Display Type | Segmented LCD; with 3 Buttons |
Electrical Wiring Size | Screw terminals; 18-24 AWG |
Enclosure Material | High impact ABS plastic |
Humidity Measurement Accuracy | ±2% from 10 to 80% RH @ 25°C (77 °F) |
Humidity Measurement Range | 0 to 100% RH |
Humidity Measurement Resolution | 0.1% RH |
Humidity Sensor Type | Thin-film capacitive; replaceable |
Input Specifications | Class 2; 20 to 30 Vdc; 24 Vac; 50 to 60 Hz |
IP Protection | IP20 |
Measurement Type | RH / Temperature |
Operating Humidity | 0 to 95% RH non-condensing |
Operating Temperature | 0 to 50 °C (32 to 122 °F) |
Output Specifications | Selectable 4 to 20 mA; 0 to 5 V; 0 to 10 V |
Outputs | Analog |
Override | Yes |
Setpoint Range | Temperature: 0 to 50 °C (32 to 122 °F) / 10 to 35 °C (50 to 95 °F); selectable Humidity: 0 to 100% RH. Fan Speed: Off; Low; Med.; High. |
Setpoint Specifications | 0-10Vdc. Temperature; humidity or fan speed (one setpoint type is selectable via dip switch) |
Setpoint | Yes |
Standards EMC | EN61000 Series - industrial immunity |
Temperature Measurement Range | 0 to 50 °C (32 to 122 °F) |
Temperature Measurement Resolution | 0.1 °C (0.1 °F) |
Temperature Sensor Type | Thermistor; 10K with 11K Shunt |