EP3331S2 | EP | Tri-S | PWM | Alg out | Press loss | Vnt on pwr | man mode | C | Veris
4 to 20 mA/0 to 10 VDC Output Vent on Power Fail Electropneumatic Transducer, EP Cover Plate
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to EP3331S2
Overview Details for EP3331S2
The EP3 series combines a microcontroller with high performance, low power coil poppet valve technology to create a system with unparalleled accuracy and proven reliability. The poppet valves used in the EP3 consume no air, eliminating unnecessary air losses in the system and allowing for efficient, long-term operation. The EP3 permits versatility, since all models feature manual override and a tri-state control option. The LCD provides easy visibility and the LED indicators provide visual status of valve operation in manual or automatic mode. All models come with SnapTrack housing.
- Poppet valve technology for quiet operation
- Manual override with set and hold feature, great for commissioning leaky systems
- Pressure loss alarm provides a contact closure if the EP3 is unable to achieve the desired output within a fixed length of time
- Fail-safe vent solenoids bleed branch pressure on power failure for added safety
- EP cover plate
- Media connection - clean, dry air, or inert gas, do not use with oxygen service
Specifications
| Item Number | EP3331S2 |
| Brand | Veris |
| Application Zone | Plant Room |
| Application | Pneumatic Actuated Dampers | Pneumatic Actuators |
| Brand | Veris |
| Dimension Depth | 1.8" (46 mm) |
| Dimension Height | 3.5" (89 mm) |
| Dimension Width | 4.9" (125 mm) |
| Direction | Unidirectional |
| Display Type | None |
| Electrical Wiring | 3-wires |
| Fail Safe | Vent on power fail |
| Fitting Material | Plastic |
| Fitting Size | 0.18" (4.3 mm) |
| Fitting Type | Male |
| Input Specifications | 4 - 20 mA | 0 - 5 V | 0 - 10 V | Tri-State | PWM |
| LED Indicator Type | Red and Green |
| Measurement Type | Electropneumatic Transducers |
| Medium | Dry Air | Inert Gas |
| Model | EP3331S2 |
| Mounting | Panel |
| Operating Humidity | 10 - 90% RH; non-condensing |
| Operating Temperature | 41 - 140 °F (5 - 60 °C) |
| Output Specifications | 4 - 20 mA | 0 - 10 V |
| Pressure Measurement Accuracy | ±1% of F.S. |
| Pressure Measurement Range | 3 - 15 psi (0.2 - 1 bar) | 0 - 20 psi (0 - 1.35 bar) |
| Pressure Output Signal | 0-10 VDC |
| Pressure Output Signal | 0-5 VDC |
| Pressure Output Signal | 4-20 mA |
| Pressure Range | 0-20 psig |
| Pressure Range | 3-15 psig |
| Pressure Sensor Type | Guage |
| Pressure Sensor w LCD | Yes |
| Product Certification | CE |
| Product Type | Sensor |
| Range | EP3 |
| Sensor | Pressure |
| Standards EMC | EN 61000-6-1 |
| Supply Voltage AC Range | 20 - 30 VAC |
| Supply Voltage DC Range | 22 - 30 VDC |