Get your Special Pricing!
Documents: CWV2
CWV2 | Sensor, CO2, Value, Wall | Veris
Sensor, CO2, Value, Wall
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to CWV2
Overview Details for CWV2
The CWV2 air quality sensor for living space is for use with BAS controllers designed to accept 4 to 20mA, 0 to 5 Vdc or 0 to 10 Vdc outputs. The CWV2 measures CO2 levels using a dual-beam, non-dispersive infrared (NDIR) technology. The CWV2 Value sensor with an accuracy of ±40 ppm ±5.5% of measured value, is ideal for bid-spec applications.
- Competitively priced sensors
- Easy installation: large wiring terminals on baseplate screw simplify installation and service
- Flexibility: field selectable outputs
- Easy to maintain: self calibrating
The CWV2 air quality sensor for living space is for use with BAS controllers designed to accept 4 to 20mA, 0 to 5 Vdc or 0 to 10 Vdc outputs. The CWV2 measures CO2 levels using a dual-beam, non-dispersive infrared (NDIR) technology. The CWV2 Value sensor with an accuracy of ±40 ppm ±5.5% of measured value, is ideal for bid-spec applications.
Specifications
Item Number | CWV2 |
Brand | Veris |
CO2 Measurement Accuracy | ±40 ppm ±5.5% of measured value |
CO2 Measurement Range | 0 to 2000ppm |
CO2 Measurement Repeatability | ±30 ppm ±4.5% of measured value |
CO2 Measurement Resolution | 1 ppm |
CO2 Response Time | =75 seconds for 90 degree step change |
CO2 Sensor Type | Dual beam on-dispersive infrared (NDIR); diffusion sampling |
Color | Matte White |
Electrical Wiring Size | Screw terminals; 18-24 AWG |
Enclosure Material | High impact ABS plastic |
Humidity Measurement Accuracy | ±2% from 10 to 80% RH @ 25°C (77 °F) |
Input Specifications | Class 2; 20 to 30 Vdc; 24 Vac; 50 to 60 Hz |
IP Protection | IP20 |
Measurement Type | CO2 |
Operating Current | 45mA |
Operating Humidity | 0 to 95% RH non-condensing |
Operating Temperature | 0 to 50 °C (32 to 122 °F) |
Output Specifications | Selectable 4 to 20 mA (3-wire); 0 to 5 V (3-wire); 0 to 10 V (3-wire) |
Outputs | Analog |
Standards EMC | EN61000 Series - industrial immunity |
Standards | CE; UL 916; RCM; ICES-003. REACH; RoHS |
Warranty | 1 Year |