Scroll to view all
Get your Special Pricing!
CW2TAXD | CO2,Wall,Touch,Temp,10K T2 | Veris
Sensor, CO2, Wall, Touchscreen, Temp, 10k Type 2 Thermistor
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to CW2TAXD
Overview Details for CW2TAXD
The Veris CW2 Series of air quality sensors for living space is a flexible multi-sensor platform for use with various brands of BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc, 0 to 10Vdc, and various thermistor outputs. CW2 Series sensors feature no-logo on the faceplate. The CW2TAXD sensor has a touch screen interface. CO2 and temperature sensors are included with all CW2 Series air quality sensors.
- Touchscreen interface
- CO2 and Temperature sensor
- High CO2 accuracy: NDIR Non-dispersive infrared (NDIR), diffusion sampling
- CO2 Accuracy: ±30 ppm ±3% of measured value
- Thermistor, 10K Type 2 Temperature sensor
- Temperature measurement accuracy ±0.1 °C
- Field Selectable outputs
- Easy to install: snap on covers with security screw simplify installation and service
- Easy Maintenance: Self Calibrating
- Lower installation and service costs with multi sensor platform
Specifications
| Item Number | CW2TAXD |
| Brand | Veris |
| CO2 Measurement Accuracy | ±30 ppm ±3% of measured value |
| CO2 Measurement Range | 0 to 2000/5000 ppm (selectable) |
| CO2 Measurement Repeatability | ±20 ppm ±1% of measured value |
| CO2 Measurement Resolution | 1 ppm |
| CO2 Response Time | <60 seconds for 90% step change |
| CO2 Sensor Type | Non-dispersive infrared (NDIR); diffusion sampling |
| Color | Matte White |
| Display Resolution | 240 x 300 px |
| Display Size | 2.4 in (61 mm) |
| Display Type | LCD; Color; Backlit; Capacititve Touchscreen |
| Electrical Wiring Size | Screw terminals; 18-24 AWG |
| Enclosure Material | High impact ABS plastic |
| Input Specifications | Class 2; 20 to 30 Vdc; 24 Vac; 50 to 60 Hz |
| IP Protection | IP20 |
| Measurement Type | CO2 / Temperature |
| Operating Humidity | 0 to 95% RH non-condensing |
| Operating Temperature | 0 to 50 °C (32 to 122 °F) |
| Output Specifications | Selectable 4 to 20 mA; 0 to 5 V; 0 to 10 V |
| Outputs | Analog |
| Override | Yes |
| Setpoint Range | Temperature: 0 to 50 °C (32 to 122 °F) / 10 to 35 °C (50 to 95 °F); selectable Fan Speed: Off; Low; Med.; High. |
| Setpoint Specifications | 0-10Vdc. Temperature or fan speed (one setpoint type is selectable via dip switch) |
| Setpoint | Yes |
| Standards EMC | EN61000 Series - industrial immunity |
| Standards | CE; UL 916; RCM; ICES-003. REACH; RoHS |
| Temperature Measurement Accuracy | ±1.0 °C |
| Temperature Measurement Range | 0 to 50 °C (32 to 122 °F) |
| Temperature Measurement Resolution | 0.1 °C (0.1 °F) |
| Temperature Sensor Type | Thermistor; 10K Type 2 |
| Warranty | 5 Years |