CW2LPXAV | CO2,Wall,LCD,Temp, Xmtr,VOC,Prot | Veris

Sensor, CO2, Wall, LCD,Temp, Transmitter, VOC, BACnet/Modbus

Brand: VerisSKU: CW2LPXAV
Veris | CW2LPXAV
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to CW2LPXAV

Overview Details for CW2LPXAV

Specifications

Item Number CW2LPXAV
Brand Veris
CO2 Measurement Accuracy ±30 ppm ±3% of measured value
CO2 Measurement Range 0 to 2000/5000 ppm (selectable)
CO2 Measurement Repeatability ±20 ppm ±1% of measured value
CO2 Measurement Resolution 1 ppm
CO2 Response Time <60 seconds for 90% step change
CO2 Sensor Type Non-dispersive infrared (NDIR); diffusion sampling
Color Matte White
Communication Specifications BACnet MSTP or Modbus via RS-485; selectable
Communication Protocol
Display Size 2.05 in (52 mm)
Display Type Segmented LCD; with 3 Buttons
Electrical Wiring Size Screw terminals; 18-24 AWG
Enclosure Material High impact ABS plastic
Humidity Measurement Linearity Included in accuracy specification
Humidity Measurement Resolution 0.1% RH
Input Specifications Class 2; 20 to 30 Vdc; 24 Vac; 50 to 60 Hz
IP Protection IP20
Measurement Type CO2 / VOC / Temperature
Operating Humidity 0 to 95% RH non-condensing
Operating Temperature 0 to 50 °C (32 to 122 °F)
Setpoint Range Temperature: Scale: 0 to 50 °C (32 to 122 °F) max.; adjustable span. Fan Speed: Off; Low; Med.; High.
Setpoint Specifications Temperature and fan speed
Setpoint Yes
Standards EMC EN61000 Series - industrial immunity
Standards CE; UL 916; RCM; ICES-003. REACH; RoHS
Temperature Measurement Accuracy ±0.2 °C (±0.4 °F) typical
Temperature Measurement Range 0 to 50 °C (32 to 122 °F)
Temperature Measurement Resolution 0.1 °C (0.1 °F)
Temperature Sensor Type Solid state; integrated circuit
VOC Measurement Accuracy ±15% of measured value
VOC Measurement Range 0 to 100% AQI for VOC
VOC Output Scale 0 to 1;000 ppb of total VOC (TVOC)
VOC Sensor Type Solid state
Warranty 5 Years