P45NAA-5C | LUBE OIL DIF PRES CONTROL; 7/60 PSI 13 36" CLOSE 9+/-3 PSI; MTG. BRKT. NONE; JUMPER NO; | Johnson Controls

Brand: Johnson ControlsSKU: P45NAA-5C
Johnson Controls | P45NAA-5C
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to P45NAA-5C

Overview Details for P45NAA-5C

LUBE OIL DIF PRES CONTROL; 7/60 PSI 13 36" CLOSE 9+/-3 PSI; MTG. BRKT. NONE; JUMPER NO;

Description

The P45 Control provides dependable, low lube oil pressure protection for refrigeration compressors. The low-adjustable factory-set pressure setting provides operation to the compressor manufacturer’s specification. A built-in time delay relay, compensated for ambient temperature, allows for pressure pick-up on start and avoids nuisance shutdowns on short duration pressure losses during the running cycle. Refer to the P45 Series Oil Pressure Cutout Controls with Built-in Time Delay Relay Product Bulletin (LIT-125445) for important product application information.

Features

  •  universal mounting
  •  trip-free manual reset
  •  ambient compensated time delay

Accessories

These controls are supplied without mounting brackets. If brackets are required, order kit number BKT38A-600R, which contains five 271-51 Angle Mounting Brackets with screws.

Applications

The P45 control is used on semi-hermetic compressors. It measures net oil pressure available to circulate oil through the compressor’s lubrication system. (Net oil pressure is the difference between oil pump pressure and the crank case pressure.)

Repair Information

If the P45 Series Lube Oil Pressure Cutout Control with Time Delay fails to operate within its specifications, replace the unit. For a replacement control, contact the nearest Johnson Controls® representative

Specifications

Item Number P45NAA-5C
Brand Johnson Controls
Category Oil Protection Controls

Contractor Rewards Program