TGW-ACN | CO/NO2, Analog, Duct, LCD, LED, Alarm | Senva Sensors (OBSOLETE)
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!

Speak With a Technical Expert

Image for Technical Expert

Documents: TGW-ACN

TGW-ACN | CO/NO2, Analog, Duct, LCD, LED, Alarm | Senva Sensors (OBSOLETE)

Brand: Senva SensorsSKU: TGW-ACN
Senva Sensors | TGW-ACN
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to TGW-ACN

Overview Details for TGW-ACN

DISCONTINUED AND REPLACED WITH TGW-ACN-A

CO/NO2, Analog, Duct, LCD, LED, Alarm

Description

Senva TG Series sensors can be ordered as individual CO or NO2 sensors or as a combination CO/NO2 sensor in a shared enclosure.

The analog output model features 2 outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost eff ective coverage of large areas. The unit can also act as a stand alone controller, utilizing the relay for exhaust fan operation or the output for direct control of a VFD.

The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-confi guration, a programmable fan relay, LED indicators, integrated display and audible alarm.

APPLICATIONS

  • Ensure adequate air fl ow in occupied spaces
  • Monitor multiple toxic gases with one mounted unit
  • Alert occupants of elevated gas levels
  • Directly control exhaust fans

FEATURES

  • Cost-eff ective dual gas sensing and control
    - Integrated display, LED indicators, audible alarm
    - Order as individual CO or NO2 sensor, or specify both sensing elements in one enclosure
  • Flexibility of analog output model
    - Menu selectable 0-5/10V, 1-5V and 4-20mA outputs (0-10V default)
    - Dual outputs support daisy chain wiring to cost-eff ectively sense and control large areas
  • Versatility with BACnet/Modbus model
    - Supports BACnet MS/TP and Modbus RTU networks
    - Auto-configuration detects network baud rate, serial format, protocol type and self-addresses
  • High reliability reduces call backs
    - Temperature compensated elements for maximum accuracy
    - UL2034 recognized electrochemical CO sensing element
    - 5 year life expectancy on CO and NO2 elements
    - Warning indicators alert occupants when element’s lifecycle is near end for replacement
    - 7-year limited warranty on electronics; 2-year on elements
  • Easy to install
    - Test mode speeds up fi eld commissioning for verifying warning indicators and relay functions
    - Push buttons and LCD to navigate setting parameters

Specifications

Item Number TGW-ACN
Brand Senva Sensors
Communication
Communication Modbus
Display LCD
Display LED
Sensor Configuration Duct
Sensor Toxic Gas

Reviews