BMXDRA0815 | Discrete output module, Modicon X80, 8 NO relay outputs, 24 to 240V AC / 24 to 125V DC | Square D by Schneider Electric
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!

Web Price:

$358.05
Availability: This product is currently available to purchase

Contact us for price breaks on large quantities!

Orders over $999 ship FREE*
*Free shipping applies within the continental US and weighing less than 50 lbs. Shipping and Returns Terms
Ship to Estimates
Are you from Chicago?
Yes / No
This item ships to
Change
Cancel


*shipping cost are estimated until you complete your order

Speak With a Technical Expert

Image for Technical Expert

Documents: BMXDRA0815

BMXDRA0815 | Discrete output module, Modicon X80, 8 NO relay outputs, 24 to 240V AC / 24 to 125V DC | Square D by Schneider Electric

Brand: Square DSKU: BMXDRA0815
Square D | BMXDRA0815
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to BMXDRA0815

Overview Details for BMXDRA0815

Discrete output module, Modicon X80, 8 NO relay outputs, 24 to 240V AC / 24 to 125V DC

Specifications

Range of Product
Modicon X80
Product or Component Type
Relay discrete output module
discrete output number
8 EN/IEC 61131-2
Discrete output logic
Positive
discrete output voltage
24...240 V 19...264 V AC, 24...125 V 5...150 V DC
electrical connection
20 ways terminal block
Network Frequency
50/60 Hz
Network frequency limits
47…63 Hz
Sensor power supply
5...150 V, 19...264 V
[Ith] conventional free air thermal current
3 A
insulation resistance
> 10 MOhm 500 V DC
power dissipation in W
3.6 W
response time on output
<= 10 ms activation, <= 13 ms deactivation
typical current consumption
40 mA 3.3 V DC, 101 mA 24 V DC
MTBF reliability
2683411 H
protection type
External short-circuit protection, External overload protection, External overvoltage protection, inductive AC, External overvoltage protection, inductive DC
Output overload protection
Use 1 fast blow fuse per channel or group of channel
output overvoltage protection
Use discharge diode on each output DC, Use RC circuit on each output AC, Use ZNO surge limiter on each output AC
Output short-circuit protection
Use 1 fast blow fuse per channel or group of channel
minimum switching current
1 mA 5 V DC
electrical durability
AC-12 200000 cycles 48 VA 24 V 32…140 °F (0…60 °C), AC-12 300000 cycles 48 VA 48 V 32…140 °F (0…60 °C), AC-12 150000 cycles 96 VA 48 V 32…140 °F (0…60 °C), AC-12 300000 cycles 110 VA 100...120 V 32…140 °F (0…60 °C), AC-12 150000 cycles 220 VA 100...120 V 32…140 °F (0…60 °C), AC-12 300000 cycles 220 VA 200...250 V 32…140 °F (0…60 °C), AC-12 150000 cycles 500 VA 200...250 V 32…140 °F (0…60 °C), AC-15 700000 cycles 10 VA 24 V 32…140 °F (0…60 °C) 0.4), AC-15 500000 cycles 24 VA 24 V 32…140 °F (0…60 °C) 0.4), AC-15 200000 cycles 48 VA 24 V 32…140 °F (0…60 °C) 0.4), AC-15 700000 cycles 10 VA 48 V 32…140 °F (0…60 °C) 0.4), AC-15 500000 cycles 24 VA 48 V 32…140 °F (0…60 °C) 0.4), AC-15 300000 cycles 48 VA 48 V 32…140 °F (0…60 °C) 0.4), AC-15 100000 cycles 96 VA 48 V 32…140 °F (0…60 °C) 0.4), AC-15 1000000 cycles 10 VA 100...120 V 32…140 °F (0…60 °C) 0.4), AC-15 300000 cycles 50 VA 100...120 V 32…140 °F (0…60 °C) 0.4), AC-15 200000 cycles 110 VA 100...120 V 32…140 °F (0…60 °C) 0.4), AC-15 70000 cycles 220 VA 100...120 V 32…140 °F (0…60 °C) 0.4), AC-15 1000000 cycles 10 VA 200...250 V 32…140 °F (0…60 °C) 0.4), AC-15 500000 cycles 50 VA 200...250 V 32…140 °F (0…60 °C) 0.4), AC-15 200000 cycles 110 VA 200...250 V 32…140 °F (0…60 °C) 0.4), AC-15 150000 cycles 220 VA 200...250 V 32…140 °F (0…60 °C) 0.4), DC-12 200000 cycles 24 W 24 V 32…140 °F (0…60 °C), DC-12 150000 cycles 48 W 24 V 32…140 °F (0…60 °C), DC-12 150000 cycles 40 W 48...60 V 32…140 °F (0…60 °C), DC-12 100000 cycles 45 W 100...125 V 32…140 °F (0…60 °C), DC-13 100000 cycles 10 W 24 V 32…140 °F (0…60 °C), DC-13 60000 cycles 24 W 24 V 32…140 °F (0…60 °C), DC-13 40000 cycles 48 W 24 V 32…140 °F (0…60 °C), DC-13 40000 cycles 40 W 48...60 V 32…140 °F (0…60 °C), DC-13 100000 cycles 15 W 100...125 V 32…140 °F (0…60 °C)
status LED
1 LED (Green) RUN, 1 LED per channel (Green) channel diagnostic, 1 LED (Red) ERR, 1 LED (Red) I/O
Net Weight
0.37 lb(US) (0.169 kg)
IP Degree of Protection
IP20
dielectric strength
1780 V AC 50/60 Hz 1 min
vibration resistance
3 gn
shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
relative humidity
0…95 % 140 °F (60 °C) without condensation
operating altitude
0...6561.68 ft (0...2000 m), 2000...5000 m with derating factor
Category
18160-MODICON M340
Discount Schedule
PC34
GTIN
3606481275608
Returnability
Yes
Country of origin
FR
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.17 in (5.5 cm)
Package 1 Width
4.33 in (11.0 cm)
Package 1 Length
4.53 in (11.5 cm)
Package 1 Weight
7.13 oz (202.0 g)
Unit Type of Package 2
S02
Number of Units in Package 2
15
Package 2 Height
5.91 in (15.0 cm)
Package 2 Width
11.81 in (30.0 cm)
Package 2 Length
15.75 in (40.0 cm)
Package 2 Weight
6.68 lb(US) (3.03 kg)