Overview Details for AM102C1070-UT-1LF
1" MixVlv 70-120F
Resideo AM102C1070-UT-1LF 1" MixVlv 70-120F is a high-quality valve designed for use in hydronic heating systems. It features a durable construction and reliable performance, ensuring long-lasting operation in demanding environments. The valve is designed to maintain a constant mixed water temperature by blending hot and cold water, making it ideal for applications such as radiant floor heating and domestic hot water systems. With its precise temperature control, this valve helps to improve energy efficiency and provide consistent comfort levels.
Specifications
- Application
- Scald prevention in Domestic water; Nursing homes; Public facilities; Automatic faucets; Industrial applications; Photo processing
- Maximum Safe Operating Pressure (psi)
- 150 psi
- Maximum Safe Operating Pressure (kPa)
- 1034 kPa
- Comments
- Low lead Content <.25% by weighted average
- Item Type
- Product
- Approvals, Canadian Standards Association
- CSA Certified
- Approvals, Others
- NSF/ANSI; IAPMO
- Connection Type
- Union NPT
- Minimum flow rate (gpm)
- 0.5 gpm
- Pipe Size (inch)
- 1 in.
- Pipe Size (DN)
- DN25
- Fluid Temperature (C)
- Cold Inlet: 4 C to 27 C; Hot Inlet: 49 C to 82 C; Mixed Outlet: 21 C to 49 C
- Fluid Temperature (F)
- Cold Inlet: 39 F to 80 F; Hot Inlet: 120 F to 180 F; Mixed Outlet: 70 F to 120 F
- Capacity (Cv)
- 1.8 Cv
- Valve Type
- Mixing Valves
- Materials (Body)
- Teflon-Coated, Nickle-Plated Low Lead Brass
- Minimum flow rate (lpm)
- 1.9 lpm
- Materials (Packing)
- EPDM O-rings
- Approvals, ASSE
- 1017 and 1070