MS-151 | Differential pressure transmitter | 4-20 mA output | selectable range 25
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!

MS-151 | Differential pressure transmitter | 4-20 mA output | selectable range 25" w.c. (5 kPa) | wall mount. | Dwyer (OBSOLETE)

Differential pressure transmitter, 4-20 mA output, selectable range 25" w.c. (5 kPa), wall mount.

Brand: DwyerSKU: MS-151
Dwyer | MS-151
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to MS-151

Overview Details for MS-151

DISCONTINUED MODEL, CONTACT TECHNICAL SUPPORT FOR REPLACEMENT OPTIONS See catalog product page for full listing

Differential pressure transmitter | 4-20 mA output | selectable range 25" w.c. (5 kPa) | wall mount.

SERIES MS MAGNESENSE® DIFFERENTIAL PRESSURE TRANSMITTER

Monitors Pressure & Air Velocity

The Series MS Magnesense® Differential Pressure Transmitter is an extremely versatile transmitter for monitoring pressure and air velocity. This compact package is loaded with features such as, field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output signal (with optional display) and the ability to select a square root output for use with Pitot tubes and other similar flow sensors.

Along with these features, the patented magnetic sensing technology providesexceptional long term performance and enables the Magnesense® DifferentialPressure Transmitter to be the single solution for your pressure and flow applications.

NIST CALIBRATION available in Product Configurator.

Please see Series AT-MS for ATEX approved.

Product Applications

  • Building pressure monitoring
  • Duct pressure monitoring
  • Fan velocity measurement
  • Zone differential pressure monitoring
  • Filter condition monitoring
  • Field selectable English or Metric ranges
  • Field upgradeable LCD display
  • Adjustable damping of output signal (with optional display)
  • Ability to select a square root output for use with pitot tubes and other similar flow sensors

Specifications

Series
MS MAGNESENSE® DIFFERENTIAL PRESSURE TRANSMITTER
Category/Type
Pressure
Type
Differential Pressure
Series
MS MAGNESENSE® DIFFERENTIAL PRESSURE TRANSMITTER
Service
Air and non-combustible compatible gases.
Wetted Materials
Consult factory.
Accuracy
±1% for 0.25" (50 Pa); 0.5" (100 Pa); 2" (500 Pa); 5" (1250 Pa); 10" (2kPa); 15" (3 kPa); 25" (5 kPa) ±2% for 0.1" (25 Pa); 1" (250 Pa) and all bidirectionalranges.
Stability
±1% FS/year.
Temperature Limits
0 to 150°F (-18 to 66°C).
Pressure Limits
1 psi maximum; operation; 10 psi; burst.
Power Requirements
10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
Output Signals
4 to 20 mA (2-wire); 0 to 5 V; 0 to 10 V (3-wire).
Response Time
300 ms.
Zero & Span Adjustments
Digital push button.
Loop Resistance
Current output: 0-1250 Ω max; Voltage output: min. loadresistance 1 kΩ.
Current Consumption
40 mA max.
Display (optional)
4 digit LCD.
Electrical Connections
4-20 mA; 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V; 3-wire: European Style Terminal Block 16 to 22 AWG.
Electrical Entry
1/2" NPS Thread. Accessory: Cable Gland for 5 to 10 mm diameter cable.
Process Connection
3/16" (5 mm) ID tubing. Maximum OD 9 mm.
Enclosure Rating
NEMA 4X (IP66).
Mounting Orientation
Diaphragm in vertical position.
Weight
8.0 oz (230 g).
Agency Approvals
CE.

Reviews