Scroll to view all
Get your Special Pricing!
Documents: ILA10
ILA10 | In-line infrared sensor | type J thermocouple | Dwyer
In-line infrared sensor, type J thermocouple
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to ILA10
Overview Details for ILA10
See catalog product page for full listing
In-line infrared sensor | type J thermocouple
Series ILA In-Line IR Sensor
15:1 Distance-to-Target Ratio, 32 to 932°F
The Series ILA In-Line IR Sensors, measure temperatures from 32 to 932°F (0 to 500°C) and provide a linear 4 to 20 mA, or thermocouple output. The 2-wire signal is compatible with almost any indicator, controller, recorder, data logger, etc., without the need for special interfacing or signal conditioning. They are suitable for most materials such as food, paper, textiles, plastics, leather, tobacco, pharmaceuticals, chemicals, rubber, coal, and asphalt.
Product Applications
- Industrial processes where non-contact temperature measurement is preferred
- Non-contact temperature measurement
- J type or 4 to 20 mA output signals
Specifications
- Series
- ILA In-Line IR Sensor
- Category/Type
- Temperature
- Type
- Sensors
- Series
- ILA In-Line IR Sensor
- Temperature Range
- 32 to 932ºF (0 to 500ºC).
- Accuracy
- 1% of reading or 1°C whichever is greater.
- Emissivity
- 0.95 (fixed).
- Distance to Target Size Ratio
- 15:1.
- Response Time
- 240 ms.
- Temperature Limits
- Ambient: 32 to 158°F (0 to 70°C).
- Power Requirement
- 24 VDC.
- Repeatability
- 0.5% of reading or 0.5°C whichever is greater.
- Outputs
- 4 to 20 mA; J type thermocouple.
- Cable Length
- 3.3' (1 m).
- Spectral Response
- 8 to 14 microns.
- Housing
- SS.
- Weight
- 3.35 oz (95 g).
- Agency Approval
- CE.