Documents: AVPT-H02C1A12
AVPT-H02C1A12 | Air velocity transmitter | 3% accuracy | 2000 FPM | 12" probe | 20" pre-wired cable | analog output | Dwyer
Air velocity transmitter, 3% accuracy, 2000 FPM, 12" probe, 20" pre-wired cable, analog output
Overview Details for AVPT-H02C1A12
Air velocity transmitter | 3% accuracy | 2000 FPM | 12" probe | 20" pre-wired cable | analog output
SERIES AVPT PENCIL STYLE AIR VELOCITY TRANSMITTER
The Series AVPT Pencil Style Air Velocity Transmitter uses thermal anemometertechnology to provide high accuracy and stable air velocity measurements in imperialand metric units. The Series AVPT can be configured with either a voltage output orBACnet MS/TP communication to provide universal inputs to a variety of monitoringequipment. Models are available with fixed cable lengths of 20 or 78 inches with flyingleads or a 5-pin M12 connector on a 24 inch cable. Probes are available in lengths of6 or 12 inches. A mounting flange included with the product provides the ability to varyinsertion depth.
Models are available in 3% or 5% accuracy to suit a variety of applications, while theoptional BACnet MS/TP communication protocol allows units to be daisy-chained toprovide access to all of the velocity and temperature measurements.
Product Applications
- VAV systems
- Building ducts
- Sensing elements have been coated with an engineered conformal coating to ensure durability and longevity
- Varying lengths for easy installation
- Functionality at temperatures below freezing
Specifications
- Series
- AVPT PENCIL STYLE AIR VELOCITY TRANSMITTER
- Service
- Clean air.
- Ranges
- 1000; 2000; 3000; or 4000 FPM (5; 10; 15; or 20 m/s); Model specific.
- Accuracy
- Standard: ±(5% reading +40 FPM); High accuracy: ±(3% reading +40 FPM); Model specific.
- Power Requirements
- 24 VAC/VDC ±20%.
- Current Consumption
- < 50 mA.
- Outputs
- Analog: 0-10 V (0-5 V configurable).
- BACnet MS/TP
- Selectable at time of order.
- Supported Baud Rate
- 9600; 19200; 38400; 57600; 76800; and 115200.
- Voltage Output Load Resistance
- 10 kΩ minimum (10 V output with AC supply); 1 kΩ minimum all other conditions.
- Electrical Connection
- Cable: Plenum rated cable with 22 AWG conductors.
- 5-Conductor Cable whip
- 20" (0.5 m) or 78" (2 m).
- 5-pin M-12
- 24" (0.6 m); model specific.
- Response Time (90%)
- 4 s; typical.
- Operational Temperature Limits
- -4 to 140°F (-20 to 60°C).
- Storage Temperature Limits
- -40 to 140°F (-40 to 60°C).
- Probe Length
- 6" or 12"; model specific.
- Enclosure Rating
- NEMA 3.
- Mounting Orientation
- Flow direction must be parallel to the sensor tip; See Installation section for details.
- Weight
- 1.4 oz (40 g); based on M12 connection with 12" probe length.
- Agency Approvals
- CE; RCM; BTL; UL plenum rated (UL tested).