Scroll to view all
Get your Special Pricing!
Documents: 651A-10
651A-10 | Temperature transmitter | Pt100 RTD input | range 32 to 212°F (0 to 100°C). | Dwyer
Temperature transmitter, Pt100 RTD input, range 32 to 212°F (0 to 100°C).
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to 651A-10
Overview Details for 651A-10
See catalog product page for full listing
Temperature transmitter | Pt100 RTD input | range 32 to 212°F (0 to 100°C).
Series 651 Temperature Transmitter
RTD or Thermocouple Input, Zero and Span Adjust, Linearized 4 to 20 mA Signal
The Series 651 Temperature Transmitter is designed for use with 2 or 3 wire Pt100RTDs or ungrounded Type K thermocouples. Thermocouple models 651TC are coldjunction compensated, automatic 32 to 160°F (0 to 70°C) with upscale burnout.
Product Applications
- Process applications where a 4 to 20 mA signal is required
- Various preset ranges available
- Pt100 or K type thermocouple models
- Standard temperature sensor head enclosure mounting
Specifications
- Series
- 651 Temperature Transmitter
- Category/Type
- Temperature
- Type
- Transmitters
- Series
- 651 Temperature Transmitter
- Input
- 2 or 3-wire Pt100 RTD (models 651A); or ungrounded Type K thermocouple (models 651TC).
- Output
- 4 to 20 mA DC; linearized.
- Transmitter Type
- 2-wire.
- Output Impedance
- 700 Ω @ 24 VDC.
- Power Requirements
- 10 to 32 VDC; reverse connection protected.
- Accuracy
- ±0.2°C plus 0.2% reading (models 651A); ±0.1% FS plus cold junction errors (models 651TC).
- Temperature Drift
- ZERO drift typical 0.02%/°C (0.09°F); SPAN typical 0.005%/°C 0.0036°F).
- Temperature Limits
- Ambient: 32 to 122°F (0 to 50°C).
- Maximum Storage Temperature
- 160°F (70°C).
- Response Time
- 10 to 90% in 200 ms (models 651A); 70% in 2 ms (models 651TC).
- Agency Approvals
- CE.