Documents: A/1K-NI-INW-2.5"-4X
A/1K-NI-INW-2.5"-4X | RTD 1000 ohm (Nickel) | Well Water Fluid Steam Temperature Sensor | Sensor Length: 2.5 inch | NEMA 4X Housing Enclosure Box | ACI
1, 000 Ohm Nickel RTD, immersion, No Well, 2.5", NEMA 4X Enclosure
Overview Details for A/1K-NI-INW-2.5"-4X
A/1K-NI-INW-2.5"-4X | RTD 1000 ohm (Nickel) | Well Water Fluid Steam Temperature Sensor | Sensor Length: 2.5 inch | NEMA 4X Housing Enclosure Box
The polycarbonate NEMA 4X, no well configuration is designed for wet environments and adds a level of corrosion resistance. It has male 1/2 inch NPT threads and the sensing element is double encapsulated to avoid sensor failures caused by moisture infiltration. ACI also standardizes with etched Teflon lead wires and wells must be ordered separately for this part. ACI immersion temperature sensors are designed for HVAC, Building Automation Systems, and light industrial applications. Specific applications include: chillers, hot water systems, tanks, and boilers. NOTE: Welded thermowells are not intended for moving water or high pressure service. Fluid velocity and wake frequency are primary factors in well failure. Machined thermowells should be used in these types of applications.
- Negative temperature coefficient
- Double encapsulated sensor
- NEMA 4X enclosure
Specifications
Item Number | A/1K-NI-INW-2.5"-4X |
Brand | ACI |
Element Type | 1000 ohm (Nickel) |
Sensing Element | RTD |
Sensor Configuration | Immersion No Well |
Sensor Housing | NEMA 4X |
Sensor Length | 2.5 inch |
Sensor | Temperature |