RM35UB330 | Modular 3 phaseVoltage control relay, Harmony, 5A, 2CO, 220…480V AC | Square D by Schneider Electric
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to RM35UB330
Overview Details for RM35UB330
Modular 3 phaseVoltage control relay, Harmony, 5A, 2CO, 220…480V AC
This Harmony RM35-UB allows monitoring of voltage control in 3-phase networks. This modular multi function 3-phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0Specifications
- Range of Product
- Harmony Control Relays
- Product or Component Type
- Voltage control relay
- Relay Type
- Voltage control relay
- Product Specific Application
- For 3-phase supply
- Relay name
- RM35UB3
- Relay monitored parameters
- Overvoltage and undervoltage between phases
- time delay
- Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
- Switching capacity in VA
- 1250 VA
- minimum switching current
- 10 mA 5 V DC
- maximum switching current
- 5 A AC/DC
- power consumption in VA
- 0…22 VA 400 V AC 50 Hz
- measurement range
- 194...528 V voltage AC 50/60 Hz
- utilisation category
- AC-12 IEC 60947-5-1, AC-13 IEC 60947-5-1, AC-14 IEC 60947-5-1, AC-15 IEC 60947-5-1, DC-12 IEC 60947-5-1, DC-13 IEC 60947-5-1, DC-14 IEC 60947-5-1
- Contacts type and composition
- 2 C/O
- reset time
- 1500 ms time delay
- maximum switching voltage
- 250 V AC/DC
- [Us] Rated Supply Voltage
- 220...480 V AC 50/60 Hz +/- 10 %
- supply voltage limits
- 194…528 V AC
- Voltage detection threshold
- 194 V
- Control circuit frequency
- 50...60 Hz +/- 15 %
- Output contacts
- 1 C/O + 1 C/O, 1 per threshold
- Nominal output current
- 5 A
- maximum measuring cycle
- 150 ms measurement cycle as true rms value
- hysteresis
- 2 %
- delay at power up
- 650 ms
- Measurement accuracy
- +/- 10 % of the full scale value
- repeat accuracy
- +/- 0.5 % input and measurement circuit, +/- 1 % time delay
- measurement error
- < 1 % over the whole range with voltage variation, 0.05 %/°C with temperature variation
- response time
- < 200 ms (in the event of a fault)
- Quality labels
- CE
- overvoltage category
- III IEC 60664-1
- insulation resistance
- > 500 MOhm 500 V DC IEC 60255-5, > 500 MOhm 500 V DC IEC 60664-1
- [Ui] rated insulation voltage
- 400 V IEC 60664-1
- operating position
- Any position without derating
- connections - terminals
- Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end, Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end, Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end, Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- tightening torque
- 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
- Housing material
- Self-extinguishing plastic
- local signalling
- for power ON LED (green), for relay ON LED (yellow)
- mounting support
- 35 mm symmetrical DIN rail conforming to EN/IEC 60715
- Electrical durability
- 10000 cycles
- Mechanical durability
- 30000000 cycles
- operating rate
- <= 360 operations/hour full load
- Safety reliability data
- B10d = 300000, MTTFd = 319.6 years
- Width
- 1.38 in (35 mm)
- Net Weight
- 0.18 lb(US) (0.08 kg)
- Functionality
- Overvoltage and undervoltage detection
- Compatibility code
- RM3
- electromagnetic compatibility
- Emission standard for industrial environments EN/IEC 61000-6-4, Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3, Immunity for industrial environments NF EN/IEC 61000-6-2
- standards
- EN/IEC 60255-1
- Product Certifications
- C-tick, GOST, CSA, GL, UL
- Directives
- 73/23/EEC - low voltage directive, 89/336/EEC - electromagnetic compatibility
- Ambient Air Temperature for Storage
- -40…158 °F (-40…70 °C)
- ambient air temperature for operation
- -4…122 °F (-20…50 °C)
- relative humidity
- 95 % 131 °F (55 °C) IEC 60068-2-30
- vibration resistance
- 0.35 mm 5…57.6 Hz)IEC 60068-2-6, 1 gn 57.6…150 Hz)IEC 60255-21-1
- shock resistance
- 5 gn IEC 60068-2-27
- IP degree of protection
- IP20 IEC 60529 terminals), IP30 IEC 60529 casing)
- pollution degree
- 3 IEC 60664-1
- dielectric test voltage
- 2 kV AC 50 Hz, 1 min
- non-dissipating shock wave
- 4 kV
- Category
- 22380-RELAYS-MEASUREMENT (RM17-RM35)
- Discount Schedule
- CP2
- GTIN
- 3389119405324
- Returnability
- Yes
- Country of origin
- ID
- Unit Type of Package 1
- PCE
- Number of Units in Package 1
- 1
- Package 1 Height
- 1.77 in (4.5 cm)
- Package 1 Width
- 3.07 in (7.8 cm)
- Package 1 Length
- 3.82 in (9.7 cm)
- Package 1 Weight
- 4.44 oz (126.0 g)
- Unit Type of Package 2
- S03
- Number of Units in Package 2
- 48
- Package 2 Height
- 11.81 in (30.0 cm)
- Package 2 Width
- 11.81 in (30.0 cm)
- Package 2 Length
- 15.75 in (40.0 cm)
- Package 2 Weight
- 14.66 lb(US) (6.649 kg)
- Warranty