AVU-2-V | Air velocity transmitter | range 0-1575 FPM (0-8 m/s) | 0-10 VDC output | 5% accuracy. | Dwyer (OBSOLETE)
Get your Special Pricing!
Log In / Create an Account for the LOWEST PRICING on our most Popular Brands!

Speak With a Technical Expert

Image for Technical Expert

AVU-2-V | Air velocity transmitter | range 0-1575 FPM (0-8 m/s) | 0-10 VDC output | 5% accuracy. | Dwyer (OBSOLETE)

Air velocity transmitter, range 0-1575 FPM (0-8 m/s), 0-10 VDC output, 5% accuracy.

Brand: DwyerSKU: AVU-2-V
Dwyer | AVU-2-V
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to AVU-2-V

Overview Details for AVU-2-V

DISCONTINUED MODEL, CONTACT TECHNICAL SUPPORT FOR REPLACEMENT OPTIONS See catalog product page for full listing

Air velocity transmitter | range 0-1575 FPM (0-8 m/s) | 0-10 VDC output | 5% accuracy.

SERIES AVU AIR VELOCITY TRANSMITTER

Ideal for Building Automation Systems, ±5% or ±8% Full-Scale Accuracy

The Series AVU Air Velocity Transmitter is ideal for a wide range of HVAC measurement and control applications, particularly in complete building control and energy management systems. The Series AVU Transmitter operates by measuring the heat loss from one of the two sensing elements in the air stream, then calculating the air velocity. Units are virtually immune to drift due to the design of the sensing element, which makes the transmitter accurate over the whole air velocity range.

Product Applications

  • Supply and exhaust fan tracking
  • Clean room systems
  • Air pollution studies and manufacturing
  • Zone control in HVAC systems
  • 4 to 20 mA or 0 to 10 V output versions
  • NEMA 6 (IP67) enclosure rating
  • AC or DC powered (loop version DC only)
  • 5% or 8% accuracy

Specifications

Series
AVU AIR VELOCITY TRANSMITTER
Category/Type
Air Quality
Type
Air Velocity Transmitters
Series
AVU AIR VELOCITY TRANSMITTER
Service
Clean air and compatible; non-combustible gases.
Accuracy
AVU: ±5% of FS;AVUB: ±8% of FS.
Response Time (90%)
5 sec (typical).
Temperature Limits
32 to 122°F (0 to 50°C).
Humidity Limit
0-90% RH; non-condensing.
Power Requirements
-A models 24 VDC +10% - 15%; -V models 24 VDC or 24 VAC +10% - 15%.
Output Signal
-A models 4 to 20 mA current loop; -V models 0 to 10 VDC.
Loop Resistance
(-A models ) 700 Ω.
Current Consumption
60 mA + output current.
Maximum Start Up Current
85 mA; 10 V.
Output Current Limit
(-V models) >10 mA.
Electrical Connections
Screw terminal. Cable gland for 4-8 mm wire (16 gage wire).
Enclosure Rating
NEMA 6 (IP67) except sensing point.
Probe Dimensions
9.45 x .75" (240 x 19 mm).
Mounting Orientation
Unit not position sensitive. Probe must be aligned with airflow.
Weight
8.8 oz (250 g).
Agency Approvals
CE.