Scroll to view all
Get your Special Pricing!
Documents: AVU-2-A
AVU-2-A | Air velocity transmitter | range 0-1575 FPM (0-8 m/s) | 4-20 mA output | 5% accuracy. | Dwyer
Air velocity transmitter, range 0-1575 FPM (0-8 m/s), 4-20 mA output, 5% accuracy.
The photo is for representation purposes only and may not be a photo of product being purchased.
Search products similar to AVU-2-A
Overview Details for AVU-2-A
See catalog product page for full listing
Air velocity transmitter | range 0-1575 FPM (0-8 m/s) | 4-20 mA output | 5% accuracy.
SERIES AVU AIR VELOCITY TRANSMITTER
Ideal for Building Automation Systems, ±5% or ±8% Full-Scale Accuracy
The Series AVU Air Velocity Transmitter is ideal for a wide range of HVAC measurement and control applications, particularly in complete building control and energy management systems. The Series AVU Transmitter operates by measuring the heat loss from one of the two sensing elements in the air stream, then calculating the air velocity. Units are virtually immune to drift due to the design of the sensing element, which makes the transmitter accurate over the whole air velocity range.
Product Applications
- Supply and exhaust fan tracking
- Clean room systems
- Air pollution studies and manufacturing
- Zone control in HVAC systems
- 4 to 20 mA or 0 to 10 V output versions
- NEMA 6 (IP67) enclosure rating
- AC or DC powered (loop version DC only)
- 5% or 8% accuracy
Specifications
- Series
- AVU AIR VELOCITY TRANSMITTER
- Category/Type
- Air Quality
- Type
- Air Velocity Transmitters
- Series
- AVU AIR VELOCITY TRANSMITTER
- Service
- Clean air and compatible; non-combustible gases.
- Accuracy
- AVU: ±5% of FS;AVUB: ±8% of FS.
- Response Time (90%)
- 5 sec (typical).
- Temperature Limits
- 32 to 122°F (0 to 50°C).
- Humidity Limit
- 0-90% RH; non-condensing.
- Power Requirements
- -A models 24 VDC +10% - 15%; -V models 24 VDC or 24 VAC +10% - 15%.
- Output Signal
- -A models 4 to 20 mA current loop; -V models 0 to 10 VDC.
- Loop Resistance
- (-A models ) 700 Ω.
- Current Consumption
- 60 mA + output current.
- Maximum Start Up Current
- 85 mA; 10 V.
- Output Current Limit
- (-V models) >10 mA.
- Electrical Connections
- Screw terminal. Cable gland for 4-8 mm wire (16 gage wire).
- Enclosure Rating
- NEMA 6 (IP67) except sensing point.
- Probe Dimensions
- 9.45 x .75" (240 x 19 mm).
- Mounting Orientation
- Unit not position sensitive. Probe must be aligned with airflow.
- Weight
- 8.8 oz (250 g).
- Agency Approvals
- CE.